A winding resistance test of a transformer is carried out as a type test routine test and also as a field test.
Transformer insulation resistance test values.
That this document list how to test specific pieces of equipment or systems.
Apply the test voltage and note the reading.
In the factory it helps in determining the following.
Adjust megger tester at 1000 v dc.
The insulation resistance test is of value for future comparison and also for determining if the transformer is to be subjected to the applied voltage test the winding insulation resistance test is a dc high voltage test used to determine the dryness of winding insulation system the test measures the insulation resistance from individual windings to.
The megger insulation tester is a small portable instrument that gives you a direct reading of insulation resistance in ohms or megohms.
Basically there are three different tests that can be done using a megohmmeter.
Insulation resistance test of transformer is divided into three parts.
The transformer neutral bushing is to be disconnected from earth during the test.
Clean the terminals of the transformer.
Steps of this test.
B kv is the rated machine terminal to terminal voltage.
The transformer neutral bushing is to be disconnected from earth during the test.
Calculation of winding temperature at the end of temperature rise test of transformer.
With a little record keeping and common sense however you can get a good picture of the insulation condition from values that are only relative.
Apply the test voltage and note the reading.
Use caution when testing.
A rated line to line voltage for three phase ac machines line to ground voltage for single phase machines and rated direct voltage for dc machines or field windings.
Calculation of the i 2 r losses in transformer.
After the required connections are made you apply the test voltage for a period of one min.
Values based on ieee std 43 2013.
Expected test results section 7 consists of sections specific to each particular type of equipment.
Use the megger test at a low voltage side.
Visual and mechanical inspection 2.
Within those sections there are typically three main bodies of information.
Value at 60 seconds after application of the test voltage is referred to as the insulation resistance of the transformer at the test temperature.
Measure insulation resistance between low voltage windings and the main body of the transformer.
Insulation resistance decreases in temperature or moisture.
Megger insulation resistance test device.
Before conducting a transformer winding resistance test it is important to observe all safety warnings and take proper precautions ensure that all equipment to be tested is properly grounded and treat all high voltage power equipment as energized until proven otherwise by using the proper lockout tagout procedures.